On Placement Of The Diesel Generator Set
Dec 01, 2016

1, indoor use, exhaust pipe must be guided outside diameter must be muffler pipe diameter, the pipe not more than 3 elbows, to ensure the smooth smoke and pipe down should be tilted 5-10 degrees, avoid water injection; if the exhaust pipe vertically installed, you must install a rain cover.
2, protection of the generator enclosure must have a solid grounding in need of neutral-point earthing of the generator, must be carried out by a professional neutral grounding and lightning protection device configuration, non-grounding neutral point earthing of the mains. Two-way switch must be very reliable with the mains to prevent transmission. Two way switch wiring reliability required inspection authorized by local power supply Department.
3, diesel power unit installation place necessary ventilation, air inlet of the generator should be enough, diesel engines-end should have good air outlet. Outlet size should be greater than the tank area is 1.5 times more than double. Old diesel generators required Foundation is made of concrete, in the spirit level must be used when installing the logging level to make the unit fixed to the levels on the basis of. Unit should have a special shock-proof with the base foot pad or bolts. Modern diesel generators do not need a concrete foundation, because modern diesel generating set has been improved, the whole unit is flat on the ground, and are equipped with shock absorbers, very convenient.